logo
  • Where we operate
    • Markets
      • Concentrated Solar Power
      • Combined Cycle Power Plants
      • Combined Heat and Power
    • Applications
      • Our Applications
      • Turbine Bypass System
      • Boiler Attemperator
      • Heater Bypass System
      • Condensate Recirculation
      • Deaerator Level Control
      • Boiler Feedwater Startup
      • Boiler Feedwater Pump Recirculation
      • Soot Blower Steam Service
      • Vent to atmosphere
  • What we do
    • Products
      • Our Products
      • Valves
        • BVT-TB steam conditioning valve
        • BVT-TBG Steam Conditioning Valve
        • BVT-PB process bypass valve
        • BVT-SC pressure reducing valve
        • BVT-SV stop valve
        • BVT-HB heater bypass valves
        • BVT-BO turbine bypass valve
        • BVT-SCG pressure reduction valve
      • Desuperheaters
        • BVT-DLP steam desuperheater
        • BVT-DLB steam attemperator
        • BVT-DLBS steam attemperator
        • BVT-DLH steam attemperator
        • BVT-DPB1 probe-style attemperator
        • BVT-DP2 probe-style desuperheater
        • BVT-DP3 probe-style desuperheater
        • BVT-DLV venturi desuperheater
      • Actuation & Control
        • BVT-PD pneumatic piston actuator
        • Hydraulics
        • BVT-MSA pneumatic diaphragm actuator
      • Spareparts & Upgrades
        • Spring-loaded Atomizing Nozzles
        • Spare parts and retrofits
        • Pneumatics
        • Hydraulics
        • BVT-Z quick change seat
        • BVT-ZP Zero Passage quick change seat
    • Services & Solutions
      • Plant Engineering
      • Field Service
      • Technical Solutions
      • BVT Remote Assist
      • BVT ranger
    • Success stories
    • Articles
      • Desuperheating
      • Pneumatics
  • About us
    • BVT Sweden
    • Contact
    • Job listings

Desuperheating

Desuperheating reduces the temperature of superheated steam, usually by injecting cooling water into the steam flow. The water evaporates and absorbs heat, so the steam leaves at a lower temperature, closer to saturation. This protects downstream equipment and gives process users steam at a controlled temperature.

Steam properties and enthalpy

Why enthalpy matters in desuperheating

Knowing the steam enthalpy at the actual pressure and temperature is the first step in sizing a desuperheater.

Specific enthalpy is the energy carried by each kilogram of steam or water. In a desuperheater, the spray water takes up heat from the steam. First the water is heated to saturation, then it evaporates, and the resulting vapor is heated to the outlet temperature. Each of these steps shows up as a change in enthalpy. The steam temperature alone does not tell you how much energy needs to be removed, but the enthalpy difference between inlet and outlet does.

Enthalpy depends on both pressure and temperature. At high pressure, the steam is close to the saturation curve and each kilogram of spray water removes relatively little superheat. At low pressure, the latent heat of evaporation is larger, so each kilogram of water absorbs more energy. Using the actual operating pressure and temperature, rather than approximate values, gives the correct spray water flow. It also gives the correct sizing for the spray water valve and the nozzles.

The enthalpy values also show how close the outlet condition is to saturation. If the outlet is set too close to the saturation temperature, the water may not evaporate completely. The remaining droplets can cause erosion, water hammer and unstable temperature control downstream.

Enter pressure and temperature in the steam properties calculator above.

Heat balance

Steam inlet

Spray water

Steam outlet


In a desuperheater, no heat is added or removed from the outside. The energy carried in by the steam and the spray water equals the energy carried out by the cooled steam. With the mass balance mout = min + mw:

min · hin + mw · hw = (min + mw) · hout

Solved for the required spray water flow:

mw = min · (hin − hout) / (hout − hw)

where min is the inlet steam flow, hin the inlet steam enthalpy, hout the outlet steam enthalpy and hw the spray water enthalpy. The water pressure must be higher than the steam pressure so that the water can be injected.

Steam inlet – kWSpray water – kWSteam outlet – kW
Energy flow Q = m · h / 3600. Inflow (top bar) equals outflow (bottom bar). Animation speed follows the energy flow in each pipe.

Choosing the outlet temperature

The right outlet temperature depends on what the steam is used for:

  • Process heating (heat exchangers, reboilers, dryers, jacketed vessels): steam gives off most of its heat when it condenses, and superheated steam transfers heat poorly. Desuperheat close to saturation, typically 3–10 °C above the saturation temperature. This keeps a small margin so that no water droplets reach the equipment.
  • Steam turbines: the steam must stay well superheated at the inlet, typically 50–150 °C or more above saturation. This keeps the steam dry through the expansion and protects the last stages against droplet erosion. Desuperheaters are used here to limit the inlet temperature to the turbine’s design value, not to approach saturation.
  • Turbine bypass and dump steam to the condenser: the steam is cooled to the temperature the condenser or the downstream piping can accept, often 20–50 °C above saturation.
  • Distribution headers and long pipelines: a moderate superheat, often 10–30 °C, compensates for heat losses so the steam is still dry at the far users.

The closer the outlet temperature is to saturation, the harder it is for the spray water to evaporate completely. Below about 5 °C of superheat, the temperature measurement becomes unreliable and unevaporated water can remain in the pipe. Allow enough straight pipe after the desuperheater, and keep a safe margin above the saturation line in the diagram below.

Steam velocity in the inlet and outlet pipes

Inlet pipe

Outlet pipe

The flows from the heat balance above can be used to check the steam velocity in the pipes before and after the desuperheater. Select a pipe size and wall thickness (ASME B36.10) for each side. The velocity is calculated as w = m · v / A, where m is the mass flow, v the specific volume at the actual pressure and temperature, and A the inner cross-section of the pipe.

The velocity matters for both the piping and the desuperheater. If the velocity is too high, the result is noise, erosion and a high pressure drop. If it is too low, the steam cannot carry and mix the spray water well. Droplets then fall out on the pipe wall and the temperature measurement becomes unstable. For superheated steam, 20–60 m/s is a common design range. Many desuperheaters need a minimum steam velocity of around 6–10 m/s for good evaporation.

Minimum straight pipe upstream and downstream

Installation
Minimum distances

The velocities above also set the straight pipe needed around the desuperheater. The rules below come from BVT general instructions M-001. They are general guidelines. If the distances cannot be achieved, contact BVT Sweden for an installation-specific calculation. Where several criteria apply, the highest value applies.

  • L1 – straight pipe upstream of the inlet. Non-uniform upstream flow creates rotational forces that strain valve parts. Bends in three dimensions just upstream are the worst case, so multiple upstream bends require about three times the distance.
  • L2 – straight pipe downstream of the water injection, up to the first bend. The droplets need time to evaporate, so L2 is a residence time multiplied by the outlet steam velocity V. Never install a desuperheater in an elbow.
  • L3 – water injection to the downstream temperature sensor, measured along the pipe. A sensor that is too close is hit by unevaporated droplets and reads too low. No branches or isolation valves may be placed between the injection point and the sensor.

Short answer: the straight pipe required after a desuperheater is set by the time the water droplets need to evaporate, so it is a residence time multiplied by the outlet steam velocity V. BVT general instructions M-001 recommend, up to the first downstream bend:

  • Separate desuperheater or attemperator: 0.1 s × V, maximum 6 m.
  • BVT-TB steam conditioning valve with mechanical atomization: 0.1 s × V, maximum 8 × the outlet inner diameter.
  • BVT-PB process bypass valve with steam-assisted atomization: 0.05 s × V, maximum 8 × the outlet inner diameter.
  • Water injection to the temperature sensor: 0.2 to 0.3 s × V depending on the water-to-steam ratio, maximum 12 m.

Example: at an outlet velocity of 40 m/s, a separate desuperheater needs 0.1 s × 40 m/s = 4 m of straight pipe before the first bend. Low superheat, cold spray water and high spray water ratios need longer distances.

Select the product type and the upstream piping below. The calculator applies the matching rule to the inner diameters and outlet velocity from the pipe velocity calculation and the water-to-steam ratio from the heat balance above, and shows the calculation for each distance.

Steam Desuperheating – physics and design considerations

This page describes the physics behind steam desuperheating by water injection: how the water is atomized into droplets, how the droplets evaporate in the superheated steam, and which steam and water properties govern the process.

1. Introduction

Superheated steam in: ṁs, T1 Desuperheated steam out: T2 Cooling water: ṁw, Tw Evaporation length TT Straight pipe run to temperature sensor feedback: controls water flow ṁw
Figure 1. Water is sprayed into the superheated steam, evaporates, and cools the steam. A downstream temperature sensor controls the water flow.

Why desuperheat?

Superheated steam from boilers or turbine extractions is often too hot for downstream equipment, heat exchangers or processes. Saturated or near-saturated steam also transfers heat far more efficiently through condensation. A desuperheater lowers the steam temperature by injecting finely atomized water, which evaporates and absorbs heat from the steam.

Heat balance

The required water flow follows from an energy balance between steam in, water in and steam out:

m˙s hs,1+m˙w hw=(m˙s+m˙w) hs,2⇒m˙w=m˙s hs,1−hs,2hs,2−hw \dot{m}_s\,h_{s,1} + \dot{m}_w\,h_w = (\dot{m}_s + \dot{m}_w)\,h_{s,2} \quad\Rightarrow\quad \dot{m}_w = \dot{m}_s\,\frac{h_{s,1} – h_{s,2}}{h_{s,2} – h_w}

where hs,1h_{s,1} and hs,2h_{s,2} are the steam enthalpies at inlet and outlet conditions and hwh_w is the cooling-water enthalpy. The outlet temperature is normally kept a margin above saturation, T2≥Tsat+5…10 KT_2 \ge T_{sat} + 5\ldots10\,\mathrm{K}, so that all water can evaporate.

The process in three steps

  1. Atomization – the nozzle breaks the water into a spray of droplets (primary breakup, section 2).
  2. Heat-up – the droplets are accelerated and heated to saturation temperature by the steam.
  3. Evaporation – the droplets evaporate at a rate described by the d²-law (section 4).

Before the steam reaches the first pipe bend, the remaining droplets must be small enough to follow the flow (section 5).

What is important for proper desuperheating

  • Small droplets. Evaporation time scales with d2d^2. Good atomization is the single most important factor.
  • Sufficient steam velocity. High relative velocity improves breakup and heat transfer (Nu\mathrm{Nu} increases with Re\mathrm{Re}) and keeps droplets suspended. Too low velocity lets droplets fall out and hit the pipe wall.
  • Adequate superheat margin. The closer the set point is to TsatT_{sat}, the smaller the driving temperature difference and the slower the evaporation.
  • Cooling-water temperature. Warmer water reaches saturation faster and atomizes better (lower viscosity and surface tension).
  • Straight pipe run. Droplets must evaporate before bends, branches or the temperature sensor; otherwise wet steam causes erosion and false temperature readings.
  • Avoid wall impingement. Spray hitting the pipe wall causes thermal shock and cracking. A thermal liner and correct spray angle protect the pipe.
  • Rangeability. Atomization must remain good across the whole load range; variable-area (spring-loaded) nozzles help maintain spray quality at low flows.
  • Sensor placement and control. The temperature sensor must be far enough downstream to measure fully evaporated, well-mixed steam.

2. Primary Breakup – the LISA Model

Nozzle steam (gas) sheet thickness h(x) ↓ wave λ = 2π/Ks amplitude ∝ e^(Ω t) 1. Sheet formation & wave growth 2. Ligaments 3. Droplets x
Figure 2. A thin conical liquid sheet leaves the nozzle. Aerodynamic waves grow until the sheet tears into ligaments, which break into droplets.

The LISA model (Linearized Instability Sheet Atomization, Senecal et al., 1999) describes how a pressure-swirl nozzle produces droplets.

Sheet velocity and thickness. The liquid leaves the nozzle with a velocity set by the pressure drop and forms a sheet of initial thickness h0h_0:

Usheet=Cv2 ΔPρl,h0=m˙lρl Usheet π do U_{sheet} = C_v \sqrt{\frac{2\,\Delta P}{\rho_l}}, \qquad h_0 = \frac{\dot{m}_l}{\rho_l\,U_{sheet}\,\pi\,d_{o}}

Dimensionless groups. The gas Weber number and the Ohnesorge number characterise the aerodynamic and viscous effects:

Weg=ρg Urel2 (h/2)σ,Oh=WelRel \mathrm{We}_g = \frac{\rho_g\,U_{rel}^2\,(h/2)}{\sigma}, \qquad \mathrm{Oh} = \frac{\sqrt{\mathrm{We}_l}}{\mathrm{Re}_l}

Wave growth. Linear stability analysis gives a growth rate Ω(k)\Omega(k) for each wave number. The fastest growing wave KsK_s dominates, and the sheet breaks up after a time τ\tau when the amplitude has grown from η0\eta_0 to the breakup amplitude ηb\eta_b:

ηb=η0 eΩsτ,ln⁡ ⁣(ηbη0)≈12,Lb=Usheet τ \eta_b = \eta_0\,e^{\Omega_s \tau}, \qquad \ln\!\left(\frac{\eta_b}{\eta_0}\right) \approx 12, \qquad L_b = U_{sheet}\,\tau

The sheet thins as it spreads, so the thickness at the breakup length and KsK_s are solved together.

Ligament diameter. Ligaments form at half-wavelength intervals, so mass conservation gives:

dL=16 hKs d_L = \sqrt{\frac{16\,h}{K_s}}

Droplet diameter. Ligaments break up by the Rayleigh–Weber mechanism:

Ddrop=1.88 dL (1+3 Oh)1/6 D_{drop} = 1.88\,d_L\,(1 + 3\,\mathrm{Oh})^{1/6}

The breakup does not produce one single droplet size but a distribution of sizes, described in the next section. Its characteristic diameters D32D_{32} and Dv90D_{v90} are the starting diameters d0d_0 for evaporation.

3. Droplet Size Distribution

100200300400500600 Droplet diameter d [µm] (illustrative) 100 %50 %0 % D32 Dv50 Dv90 (90 % of volume below) Volume distribution q(d) Cumulative volume Q(d)
Figure 3. Typical spray droplet size distribution (Rosin–Rammler, n = 3). The blue area shows how the liquid volume is spread over droplet sizes; the orange curve is the cumulative volume fraction.

A spray always contains a range of droplet sizes. Because evaporation and heat transfer depend strongly on diameter, the distribution is summarised by a few characteristic diameters. For pressure-swirl nozzles the Rosin–Rammler distribution is commonly used:

Q(d)=1−exp⁡ ⁣[−(dX)n] Q(d) = 1 – \exp\!\left[-\left(\frac{d}{X}\right)^{n}\right]

where Q(d)Q(d) is the fraction of the liquid volume contained in droplets smaller than dd, XX is a characteristic size and nn describes the spread (typically 2–4; a higher nn means a more uniform spray).

Sauter mean diameter D32

D32=∑Ni di3∑Ni di2 D_{32} = \frac{\sum N_i\,d_i^3}{\sum N_i\,d_i^2}

The diameter of a droplet with the same volume-to-surface ratio as the whole spray. Since heat transfer occurs through the surface and the energy needed is set by the volume, D32 is the best single measure of the average evaporation rate and of the number of droplets, N=6V/(πD323)N = 6V / (\pi D_{32}^3).

Dv90

Q(Dv90)=0.9  ⇒  Dv90=X (ln⁡10)1/n Q(D_{v90}) = 0.9 \;\Rightarrow\; D_{v90} = X\,(\ln 10)^{1/n}

90 % of the liquid volume is in droplets smaller than Dv90. The largest droplets evaporate last, so Dv90 governs the required evaporation length and the risk of wet steam reaching bends or the temperature sensor. It is the conservative design value.

Always D32 < Dv50 < Dv90. Because evaporation time scales with d2d^2, a droplet at Dv90 that is 1.5 times larger than D32 needs about 2.25 times longer to evaporate.

4. Droplet Evaporation – the d²-Law

Superheated steam T∞ > Tsat u∞ (relative velocity) q̇ = h (T∞ − Td) ṁ = q̇ · A / hfg vapour joins the steam flow droplet diameter d(t) 1. InjectionCold droplet, T0 < Tsat 2. Heat-upHeated to Tsat 3. Evaporationd² decreases linearly 4. CompleteSteam desuperheated d²-law t d² d² = d0² − K·t heat-up t_heat t_life
Figure 4. Heat from the superheated steam heats the droplet to saturation temperature, after which it evaporates and the droplet diameter shrinks according to the d²-law.

Heat from the superheated steam is transferred by convection to the droplet surface. The droplet first heats to saturation temperature, then evaporates at a rate m˙=q˙ A/hfg\dot{m} = \dot{q}\,A / h_{fg}. The generated vapour cools (desuperheats) the steam.

The d²-law is the classical result for a droplet evaporating in a hot gas: once the droplet has reached saturation temperature, the square of its diameter decreases linearly with time:

d(t)2=d02−K t d(t)^2 = d_0^2 – K\,t

It follows from an energy balance on the droplet. The convective heat flow scales with the diameter, while the droplet mass scales with d3d^3:

Q˙=πd kg Nu (T∞−Tsat),−ddt ⁣(ρlπd36)hfg=Q˙    ⇒    d(d2)dt=−K \dot{Q} = \pi d\,k_g\,\mathrm{Nu}\,(T_\infty – T_{sat}), \qquad -\frac{d}{dt}\!\left(\rho_l \frac{\pi d^3}{6}\right) h_{fg} = \dot{Q} \;\;\Rightarrow\;\; \frac{d(d^2)}{dt} = -K

With the Spalding transfer number included, the evaporation constant for a droplet in still steam becomes:

K=8 kgρl cp,g ln⁡(1+B),B=cp,g (T∞−Tsat)hfg K = \frac{8\,k_g}{\rho_l\,c_{p,g}}\,\ln(1 + B), \qquad B = \frac{c_{p,g}\,(T_\infty – T_{sat})}{h_{fg}}

where kgk_g and cp,gc_{p,g} are the steam thermal conductivity and specific heat, ρl\rho_l is the water density and hfgh_{fg} the latent heat. Relative velocity enhances evaporation through the Ranz–Marshall correlation, which scales KK by Nu/2\mathrm{Nu}/2:

Nu=2+0.6 Re1/2 Pr1/3 \mathrm{Nu} = 2 + 0.6\,\mathrm{Re}^{1/2}\,\mathrm{Pr}^{1/3}

Reading the chart: the short, nearly flat segment is the heat-up period theatt_{heat} where the droplet warms to TsatT_{sat} with little mass loss. After that, d2d^2 falls along a straight line with slope −K-K until the droplet disappears at tlifet_{life}

5. Centrifugal Tracking in Pipe Bends

Impingement (erosion, thermal shock) Steam + spray from desuperheater Small droplets (St ≪ 1) follow the steam through the bend Large droplets (St ≳ 1) cannot turn and hit the outer wall Rc Required straight pipe L: Dv90 must shrink below d_limit before the bend
Figure 5. Small droplets follow the steam through the bend, while large droplets cannot turn and impinge on the outer wall.

When the steam turns in a bend, every droplet in it is pushed outward. Whether a droplet turns with the steam or keeps going and hits the outer wall depends on the Stokes number: how slowly the droplet responds to the steam compared with how quickly the steam turns.

St=ρl d2 U18 μg Rc \mathrm{St} = \frac{\rho_l\,d^2\,U}{18\,\mu_g\,R_c}

where ρl\rho_l is the water density, dd the droplet diameter, UU the steam velocity in the pipe, μg\mu_g the steam dynamic viscosity and RcR_c the bend centreline radius (typically 1.5×1.5 \times pipe ID). Droplets with St≪1\mathrm{St} \ll 1 follow the steam; droplets with St≳1\mathrm{St} \gtrsim 1 are thrown out of the flow.

Limiting droplet diameter

Requiring St≤Stlimit\mathrm{St} \le \mathrm{St}_{limit} (typically 0.1) gives the largest droplet allowed to reach the bend:

dlimit=18 μg Rc Stlimitρl U d_{limit} = \sqrt{\frac{18\,\mu_g\,R_c\,\mathrm{St}_{limit}}{\rho_l\,U}}

A tighter bend or faster steam gives a smaller dlimitd_{limit}, which is stricter.

Required straight pipe distance

The droplets shrink as they evaporate downstream of the nozzle. The required straight length is the distance at which

Dv90(L)≤dlimit D_{v90}(L) \le d_{limit}

Dv90 is used because the coarse tail of the spray, not the average droplet, decides how much water hits the wall.

How the limit relates to the straight pipe distance:
  • If Dv90 at the nozzle is already below dlimitd_{limit}, this criterion requires no straight pipe (distance 0).
  • Otherwise the distance grows with how far Dv90 has to shrink. Because of the d²-law, the time needed scales roughly with Dv902−dlimit2D_{v90}^2 – d_{limit}^2.
  • Higher steam velocity has two effects: it lowers dlimitd_{limit}, and it also carries the droplets further before they have shrunk. Both lengthen the required pipe.
  • A larger bend radius (long-radius elbow) raises dlimitd_{limit} and shortens the required distance.

The minimum distance from the injection point to the first bend is the largest of three criteria: the required evaporated mass fraction, centrifugal tracking, and momentum relaxation (the droplets reaching the steam velocity).

6. How Steam / Water Properties Affect Desuperheating

The example values below refer to a reference case of water at 200 bar / 150 °C injected into steam at 100 bar / 400 °C, with one parameter changed at a time. They illustrate trends and are not universal.

Water (cooling liquid)
Steam

Pressure

  • Mainly affects nozzle operation and sheet velocity via the pressure drop.
  • Water is nearly incompressible – minimal effect on evaporation (200 → 400 bar: ≈ 1 %).

Pressure

  • Higher pressure → higher density → lower velocity at constant m˙=ρ v A\dot{m} = \rho\,v\,A.
  • Raises TsatT_{sat}, reducing the driving temperature difference.
  • 100 → 150 bar: time 102.8 → 160.2 ms (+56 %), distance 2.37 → 2.19 m (−8 %).

Temperature

  • Less sensible heat needed to reach saturation, Q=m˙ (hsat−hw)Q = \dot{m}\,(h_{sat} – h_w).
  • Lower surface tension and viscosity → better atomization.
  • Above TsatT_{sat} at steam pressure, part of the water flashes immediately.
  • 150 → 250 °C: distance ≈ −13 %.

Temperature

  • Sets the driving force, q˙=h (Tsteam−Tdroplet)\dot{q} = h\,(T_{steam} – T_{droplet}).
  • Superheat provides the evaporation energy, E=m˙s (hs,1−hs,2)E = \dot{m}_s\,(h_{s,1} – h_{s,2}).
  • 400 → 300 °C: time 102.8 ms → 1.57 s, distance 2.37 → 1.92 m.

Flow rate

  • More water → more droplets, N=6 m/(ρl π D323)N = 6\,m / (\rho_l\,\pi\,D_{32}^3), and a thicker sheet.
  • Sub-linear effect: 12 000 → 6 000 kg/h changes distance by only ≈ 1 %.
  • Must stay within nozzle capacity.

Flow rate

  • Velocity v=m˙/(ρ A)v = \dot{m} / (\rho\,A); higher Re improves heat transfer.
  • 500 000 → 200 000 kg/h: time +151 %, distance nearly unchanged (+1 %).
  • Typically m˙s/m˙w≥10\dot{m}_s / \dot{m}_w \ge 10 for sufficient heat capacity.

Residence time, velocity and distance

Droplets need sufficient time in the steam to absorb heat, and the required pipe length is the product of velocity and time. This explains the counter-intuitive trends above:

Fast steam (low pressure)Slow steam (high pressure)
Lower density
Higher velocity
Shorter residence time
More distance needed
Higher density
Lower velocity
Longer residence time
Less distance needed
  • Temperature governs the heat-transfer rate.
  • Velocity governs the residence time available per metre of pipe.
  • Distance is velocity × time and can decrease even when time increases.

Design recommendations

  • To reduce the evaporation distance: use warmer cooling water, keep an adequate superheat margin, produce small droplets and avoid excessive steam velocity.
  • Water pressure mainly affects nozzle operation, not evaporation itself.
  • Steam pressure affects velocity more than thermodynamics (higher pressure → lower velocity at constant mass flow).
  • consider multiple nozzles for very high flows.

Frequently asked questions about desuperheating

What is steam desuperheating?

Desuperheating reduces the temperature of superheated steam, usually by injecting cooling water. The water absorbs heat as it warms and evaporates, bringing the steam closer to its saturation temperature at the operating pressure.

Why is enthalpy used to calculate spray water demand?

An enthalpy balance accounts for the energy in the inlet steam, spray water and outlet steam. Temperature alone does not capture the energy needed to heat and evaporate the injected water. The calculator above uses steam and water properties to calculate the required water flow.

Why do droplet size and atomization matter?

Smaller droplets provide more surface area relative to their volume and generally evaporate faster. Atomization and the droplet size distribution affect how much distance is needed for the injected water to evaporate.

Why are straight pipe distances needed around a desuperheater?

Straight pipe lengths provide time for the spray water to evaporate before the first bend, downstream equipment and the temperature sensor. BVT recommends 0.1 s × the outlet steam velocity after a separate desuperheater (maximum 6 m) and 0.2 to 0.3 s × the velocity to the temperature sensor (maximum 12 m). Pipe bends can change droplet trajectories and increase the risk of wall contact. See minimum straight pipe for all rules and a calculator.

Follow us

Facebook
Linkedin

Our partners

HP Valves B.V.
Key Valve Technologies LTD

Factory Support Office

Industrigatan 1-3
661 32 Säffle
SWEDEN

Sales Office

BVT Sweden AB
Körkarlsvägen 8
SE-653 46 Karlstad
Sweden

Factory Address

Industrigatan 1
661 32 Säffle
Sweden

© 2019 BVT Sweden