BVT-SV Stop Valve
Angle-body stop valve for steam and water lines — tight shut-off up to MSS SP 61, up to 500 mm seat diameter, ANSI 4500, 620 °C

Overview
The BVT-SV is an angle-body stop valve from BVT Sweden designed for the harsh environment of a modern fossil-fueled power plant. It can be used on both the water line and the steam line wherever a tight shut-off is required, and is typically placed upstream of a turbine bypass valve or a spray water control valve.
Design
The homogeneous wall thickness of the forged body minimizes material stress, and the corrosion resistant alloy on the plug and stem is surface treated to provide sufficient hardness. The balanced plug design reduces the required actuating forces, allowing smaller and pneumatic actuators, and the outlet pressure recovery cone reduces the pressure drop over the valve. Maintenance is safe and easy thanks to the pressure seal bonnet.
Applications
Isolation upstream of control valves
non-linear control characteristic that an undersized stop valve with a reduced bore causes upstream of a control valve.
Typical turbine bypass arrangement
In a turbine bypass system, BVT-SV valves are used on both sides of the bypass:
- a BVT-SV steam stop valve upstream of the BVT-TB steam turbine bypass valve, branched from the main steam line ahead of the steam turbine;
- a BVT-SV water stop valve together with a spray water control valve on the spray water line;
- downstream, a BVT-DLP multi-nozzle desuperheater where additional desuperheating is required.
Designed for maintenance
The bonnet is held by a segmented ring and retainer rather than a bolted flange, so the complete trim — bonnet, plug and stem — is lifted out of the body from above once the actuator and yoke are removed. The valve can stay welded in the pipeline. Step-by-step procedures are given in product manual M-012.
Typical markets
- Fossil-fueled power plants
- Combined heat and power (CHP) plants
- Biomass and waste-to-energy plants
- Industrial steam and feedwater systems
Specifications
| Valve sizes | Up to 500 mm seat diameter |
|---|---|
| Pressure class | Up to ANSI 4500 (higher rating on request) |
| Design temperature | 620 °C as standard (650 °C on request) |
| Leakage class | ANSI Class V, MSS SP 61 |
| Body type | Angle body |
| Media | Steam or water |
| Regulatory requirements | ASME, EN, PED, IBR, CRN. Manufactured under ISO 9001 and ISO 14001. |
| Materials | Forged material adapted to connecting pipe material |
| Bonnet | Pressure seal bonnet |
| Actuation | Pneumatic, hydraulic or electrical |
| Connections | Fully customizable inlet and outlet connections |
| Options | Live load gland seal packings |
Key features
- Fully customizable inlet and outlet connections.
- Complies with ASME, EN and PED.
- Forged valve body with uniform thickness, and trim design optimized to withstand thermal cycling.
- Tight shut-off up to MSS SP 61.
- Balanced plug design requires smaller actuating forces, allowing smaller and pneumatic actuators.
- Outlet pressure recovery cone reduces the pressure drop over the valve.
- Pressure seal bonnet for simpler and quicker maintenance — no special tools necessary.
- Compatible with pneumatic, hydraulic and electrical actuation.
- Optimized packing design.
Actuation options
Pneumatic actuation
BVT valves can be equipped with the BVT-PD linear pneumatic piston actuator, mounted on top of the valve with a coupling to the valve stem. Each actuator is sized to the force requirements of the valve and to the customer’s stroke time and functional requirements. It is also available as an upgrade for existing valves.
A positioner modulates the actuator from a 4–20 mA set-point signal, with volume boosters added where higher stroke speed is needed. By default the actuator has a quick open or quick close function: if the supply pressure drops below a set level, the modulating operation is overridden and the valve is driven to its safe position, using air stored in an air tank (double acting) or a spring (single acting).

| Types | Double acting or single acting (spring open or spring close); modulating or on/off |
|---|---|
| Air supply | 4 – 10 bar |
| Operating temperature | −20 to 80 °C (standard) |
| Cylinder sizes | Up to 900 mm |
| Protection | Components IP65/IP67; cylinder corrosion protection ISO 12944 C4 or C5M; ANSI 316 tubes and fittings |
| Standard accessories | Air filter regulator, positioner, pressure sensing valve for quick function |
| Optional accessories | Volume boosters, solenoid valves, limit switches, position transmitter, top or side mounted hand wheel |
| Compliance | ASME, PED, ISO 9001/14001; ATEX and SIL as option |
Electro-hydraulic actuation
Commissioning tools and hydraulic pipes, fittings and hoses are also available.
Installation, commissioning and maintenance
from BVT product manual M-012 and general instructions M-001.
Important: all BVT steam valves are designed for dry steam. Wet steam, condensate and magnetite damage valves, and such damage is not covered by warranty. Drains and vent valves must take care of pipe prewarming.
Minimum straight pipe upstream
Non-uniform upstream flow patterns create rotational forces that strain valve parts. The straight pipe upstream of the valve inlet (L1) must therefore exceed the values below. Where multiple criteria apply, the highest value must be used.
| Condition | L1 must exceed |
|---|---|
| Single upstream bend, Ø < 200 mm | 1 metre |
| Single upstream bend, Ø 200–400 mm | 5 × Ø |
| Single upstream bend, Ø > 400 mm | 3 × Ø |
| Multiple upstream bends, Ø < 200 mm | 3 metres |
| Multiple upstream bends, Ø 200–400 mm | 15 × Ø |
| Multiple upstream bends, Ø > 400 mm | 9 × Ø |
Combined with a control valve
The angle-style BVT-SV can be welded directly to the inlet connection of a BVT steam conditioning valve as a single unit. BVT must be informed in advance if such an arrangement is planned. A correctly sized stop valve avoids the high pressure drop, noise and vibration caused by undersized stop valves with a reduced bore upstream of a control valve.
Insulation
Any valve intended for hot service must be insulated. Thermal insulation should be applied to all exterior surfaces of the valve body and bonnet, and should help keep the body adequately warm while the valve is closed. Proper insulation minimises heat loss, maintains thermal stability, reduces the risk of condensation and water hammer, and improves personnel safety.
- Insulate the valve body, inlet and outlet piping, and adjacent flanges.
- Do not insulate actuators, positioners or other temperature-sensitive electrical equipment — the actuator and its accessories must be protected from excessive heat.
- Do not cover the yokes or add material that makes removing valve internals difficult.
- Ensure the insulation does not interfere with plug or stem movement.
- The insulation must not trap condensate around the valve body.
Insulation also provides noise attenuation. A −10 dBA arrangement uses 1 mm cladding steel plate over 300 mm mineral wool at 200 kg/m³ density. A −15 dBA arrangement adds a heavy self-adhesive noise damping layer (approx. 7 kg/m²) and a 50 mm mineral wool layer between two cladding plates.
Body material temperature limits
| Carbon steel (internals Tenifer surface hardened) | 480 °C |
|---|---|
| Low alloy steel | 580 °C |
| 13CrMo4-5 / ASTM Gr.12 | 580 °C |
| 11CrMo9-10 / ASTM Gr.22 | 580 °C |
| X10CrMoVNb9-1 / ASTM Gr.91 | 580 °C |
| Low alloy steel (internals Cobalt hard faced) | 650 °C |
Before welding into the pipeline
- Verify that the installation direction is correct, and that any arrow on the valve body points in the same direction as the flow in the pipe system.
- Align the pipe ends properly so the valve is not subjected to unnecessary strain.
- Remove the valve trim before welding the valve into the pipeline.
- Remove any commissioning tools (hydrotest, blowout, etc.) before welding.
- Welding and any necessary heat treatment are the contractor’s responsibility and must be performed in compliance with applicable standards by qualified personnel.
Commissioning and steam blowing
Debris generated during installation or major repair can damage valve trim and sealing surfaces and cause improper valve operation. Steam blowing removes loose particles from the pipework, but the procedure itself can severely damage trim parts, so protective equipment such as a blow out tool, blow through tool or sacrificial trims must be installed first. BVT must be informed of the planned steam blowing method in advance and can supply the required tools.
| Steam temperature | 50 – 100 °C above saturation point |
|---|---|
| Steam velocity | More than 50% of maximum steam velocity, and at least 70 m/s |
| Max. temperature for BVT steam blowing tools | 425 °C as standard |
If the steam velocity is too low, particles may not be carried along and can fall back into the pipework where they are difficult to detect.
Maintenance notes
- Confirm that the pressure vessel is depressurized and sufficiently cooled down before starting any work, and wear protective gloves, clothing and eye-wear.
- Before maintenance on a valve in an operational facility, a double block-and-bleed configuration must be installed upstream. Each component in the block-and-bleed system must be individually proven for the highest expected pressure.
- Ensure the packing gland is firmly tightened before pressurizing the valve. Never remove the gland nut or flange while the valve is pressurized.
- Ensure drain and vent valves are open and discharging.
- The pressure seal must be replaced after every disassembly.
- Stem packing rings must be replaced after every disassembly.
- The valve and yoke must never be lifted using the actuator or eye bolts installed on the actuator.
- If live load is used, note the compressed height of the belle-ville washer sets before removing the gland yoke nuts.
- No alteration should be made to any valve without the involvement of BVT service engineers.
Frequently asked questions
- What is the BVT-SV stop valve?
- An angle-body stop valve from BVT Sweden designed for the harsh environment of modern fossil-fueled power plants, providing tight shut-off on steam or water lines.
- Where is the BVT-SV typically installed?
- Upstream of a turbine bypass valve or a spray water control valve, wherever tight shut-off is required.
- Can the BVT-SV be used for both steam and water?
- Yes — it can be used on both the water line and the steam line.
- What leakage class does the BVT-SV meet?
- ANSI Class V or MSS SP 61.
- What sizes and pressure ratings are available?
- Up to 500 mm seat diameter and up to ANSI 4500 (higher ratings on request).
- What is the maximum design temperature?
- 620 °C as standard and 650 °C on request.
- Why does the BVT-SV have a low pressure drop?
- The outlet pressure recovery cone reduces the pressure drop over the valve.
- Which standards does it comply with?
- ASME, EN, PED, IBR and CRN. BVT Sweden manufactures under ISO 9001 and ISO 14001.
- How is the BVT-SV actuated?
- Pneumatic, hydraulic or electrical actuation. The balanced plug reduces actuating forces, allowing smaller and pneumatic actuators.
- How is the BVT-SV maintained?
- The pressure seal bonnet makes maintenance safe and easy, with no special tools necessary, and the trim is lifted out from above while the valve stays in the pipeline. The pressure seal and stem packing rings are replaced after every disassembly. See product manual M-012.
Download
Download the BVT-SV stop valve brochure (PDF, document B-009)
refer to product manual M-012 BVT-SV and to the general instructions for BVT valves and desuperheaters in M-001, or contact BVT Sweden.
Recommended spare parts
BVT recommends keeping the following BVT-SV parts in stock (source: product manual M-012). Contact BVT Sweden for a quote.
- Gland yoke and gland
- Complete segment ring
- Bonnet gasket (pressure seal)
- Cage
- Plug / stem assembly
- Seat
- Stem packings
- Stem guide
Related BVT products
About BVT Sweden
BVT Sweden AB was started with the ambition of becoming world leading in critical applications in process steam and thermal power plant turbine bypass. Based in Säffle, Sweden, BVT Sweden employs experts with over 30 years of experience in turbine bypass, steam conditioning, temperature control, design and manufacturing processes. BVT designs turbine bypass valves and selects actuation to fit each customer’s requirements. Products are optimized on a per-order basis, and include steam conditioning valves, pressure reduction valves, stop valves, desuperheaters and spray water control valves.